The Botswana Innovation Hub (BIH) presently under construction is strategically located on a new 57 hectare innovation park, near the Sir Seretse Khama International Airport in Gaborone, the capital city and business centre of Botswana.
The Hub, which creates the impetus and focal point of the park shall provide state-of-the art facilities to attract domestic, regional and global knowledge-intensive high-tech innovation companies.
This new ±46,000 m² iconic building development of futuristic architectural appearance, consists of three multi-storey blocks (referred to as Bars), sharing a common podium housing a 23,000 m² semi-enclosed super-basement carpark and service plantrooms beneath.
As part of the building’s sustainability drive, an undulating green roof provides home for indigenous grasses, whilst further merging the building form into the surrounding site’s landscaping. Feature roof overhangs, favourable building orientation, a highly bespoke façade, courtyards accommodating the amenity gardens and extensive horizontal bris soleil structures all combine to provide the building with extensive passive solar shading. These features are further enhanced by a high performance building façade, low water usage faucets and a strategic collection of surface water for irrigation purposes.
FOCUS ON HVAC
The building is designed to exploit the benefits of exposing the building’s structural thermal mass to moderate the internal environment within recognised thermal comfort criteria. This is achieved by effectively circulating a conditioned air supply through exposed ‘TermoDeck’ proprietary hollow-core concrete slabs, which form the floors and ceilings/roofs of the building structure. Such approaches typically using the thermal capacity of concrete are often referred to as Fabric Energy Storage (FES) systems or Thermally Active Buildings (TABS).
At BIH one of the main savings is in maximum electrical demand charges, as the concrete slab is pre-cooled during the night also using the free-cooling, when suitable outdoor temperatures prevail. As a result, the maximum daytime peak power consumption can be reduced by up to 50%, compared to similar buildings using conventional air conditioning and construction methods in Botswana.
Both chilled and heating water is generated by a combination of three INTEGRA multi-purpose ERACS2-Q XL-CA 2722 and one high efficiency air cooled chiller i-FX (1+i) CA 2722, all supplied by Climaveneta. These machines provide the building with a total space cooling and heating capacity of up to 2,477 kW and 1,764 kW respectively. All the units can operate at full load in parallel to meet the peak cooling loads. This arrangement allows for one machine to be off-line for repair or maintenance, whilst still being able to meet the building’s cooling load throughout most of the year. The multi-purpose INTEGRA units are able to operate in either cooling-only, cooling with simultaneous heating (this operating mode will be used predominantly during mid-season, giving EER’s of up to 9.3) and heating-only mode depending on the prevailing cooling/ heating loads of the building. The i-FX (1+i) CA 2722 chiller is primarily used when peak cooling loads are required, however all the units are operated on a “lead-leg” duty share basis. The four Climaveneta machines work with a four-pipe variable primary and secondary chilled and heating water circuit pipework arrangement.
www.climaveneta.com